Difference between revisions of "M-BUS"
From Teknologisk videncenter
m |
m |
||
(16 intermediate revisions by the same user not shown) | |||
Line 4: | Line 4: | ||
|Meter-BUS or short M-BUS which is designed mainly for remote reading of water meter, gas or electricity meters - not to be confused with [[Smart-BUS]] or short S-BUS is designed mainly for home automation | |Meter-BUS or short M-BUS which is designed mainly for remote reading of water meter, gas or electricity meters - not to be confused with [[Smart-BUS]] or short S-BUS is designed mainly for home automation | ||
|} | |} | ||
+ | [[image:MBusLogo240.svg|right|200px]] | ||
==Physical layer== | ==Physical layer== | ||
− | Master to slave: 36 Volt = 1 - 24 Volt = 0 | + | *Master to slave: 36 Volt = 1 - 24 Volt = 0 |
− | Slave to Master: Draws < 1,5 mA = 1 - draws11-20 mA = 0 | + | *Slave to Master: Draws < 1,5 mA = 1 - draws11-20 mA = 0 |
− | Baudrate: 300 - 9600 | + | *Baudrate: 300 - 9600 |
− | Cable: Two-wire standard telephone cable (JYStY N20.8 mm) | + | *Cable: Two-wire standard telephone cable (JYStY N20.8 mm) |
− | Max cable length: 350 Meter (Lower baud rates up to 1000 Meter - but restricted power not below 12 V max capacitance 180 nF) | + | *Max cable length: 350 Meter (Lower baud rates up to 1000 Meter - but restricted power not below 12 V max capacitance 180 nF) |
− | Power: Up to 27 Watt through the cable = 0,75 A | + | *Power: Up to 27 Watt through the cable = 0,75 A |
− | Slaves: Up to 250 in a single segment | + | *Slaves: Up to 250 in a single segment |
− | Repeater: Also called a master and typically is an M-BUS to RS232 converter attached to a host | + | *Repeater: Also called a master and typically is an M-BUS to RS232 converter attached to a host |
− | Plug: No standard | + | *Plug: No standard |
− | M-BUS slave example: [https://www.mikroe.com/m-bus-slave-click MIKROE-4137 M-BUS SLAVE CLICK] | + | *M-BUS slave example: [https://www.mikroe.com/m-bus-slave-click MIKROE-4137 M-BUS SLAVE CLICK] |
− | Transceiver example: [https://download.mikroe.com/documents/datasheets/tss721a_datasheet.pdf TI-TSS721A] | + | **Transceiver example: [https://download.mikroe.com/documents/datasheets/tss721a_datasheet.pdf TI-TSS721A] |
+ | *M-BUS master example: [https://www.mikroe.com/m-bus-master-click MIKROE-3880 M-BUS MASTER CLICK] | ||
+ | *[https://oms-group.org/en/open-metering-system/oms-specification OMS-Group] - Extension of M-BUS and wM-BUS | ||
− | See [https://m-bus.com/documentation-wired/04-physical-layer M-BUS physical layer]] | + | |
+ | *See [https://m-bus.com/documentation-wired/04-physical-layer M-BUS physical layer]] | ||
==Links== | ==Links== | ||
+ | *[https://m-bus.com/downloads M-BUS Documentation] (Loads PDF) | ||
+ | *[[m-bus Linux]] | ||
*https://m-bus.com/ (Good documentation) | *https://m-bus.com/ (Good documentation) | ||
+ | *[https://github.com/rscada/libmbus libmbus is an open source library for the M-bus (Meter-Bus) protocol] | ||
+ | *[https://github.com/rscada/libmbus/tree/master/mbus libmbus on github] (Newest??) | ||
+ | **[http://www.rscada.se/libmbus/doc/libmbus-api.pdf libmbus API] | ||
+ | *[https://stockshed.uk/files/kamstrup/M-Bus%20Master%20-%20Installation%20and%20User%20Guide%20-%20English.pdf Kamstrup M-Bus mater Multiport 250D] (PDF) | ||
+ | *[https://www.kamstrup.com/en-en/heat-solutions/meters-devices/meters/multical-603/documents Kamstrup MUTICAL 603 Heat Meter] | ||
[[Category:IoT]] | [[Category:IoT]] |
Latest revision as of 07:35, 22 November 2023
Meter-BUS or short M-BUS which is designed mainly for remote reading of water meter, gas or electricity meters - not to be confused with Smart-BUS or short S-BUS is designed mainly for home automation |
Physical layer
- Master to slave: 36 Volt = 1 - 24 Volt = 0
- Slave to Master: Draws < 1,5 mA = 1 - draws11-20 mA = 0
- Baudrate: 300 - 9600
- Cable: Two-wire standard telephone cable (JYStY N20.8 mm)
- Max cable length: 350 Meter (Lower baud rates up to 1000 Meter - but restricted power not below 12 V max capacitance 180 nF)
- Power: Up to 27 Watt through the cable = 0,75 A
- Slaves: Up to 250 in a single segment
- Repeater: Also called a master and typically is an M-BUS to RS232 converter attached to a host
- Plug: No standard
- M-BUS slave example: MIKROE-4137 M-BUS SLAVE CLICK
- Transceiver example: TI-TSS721A
- M-BUS master example: MIKROE-3880 M-BUS MASTER CLICK
- OMS-Group - Extension of M-BUS and wM-BUS
- See M-BUS physical layer]
Links
- M-BUS Documentation (Loads PDF)
- m-bus Linux
- https://m-bus.com/ (Good documentation)
- libmbus is an open source library for the M-bus (Meter-Bus) protocol
- libmbus on github (Newest??)
- Kamstrup M-Bus mater Multiport 250D (PDF)
- Kamstrup MUTICAL 603 Heat Meter