Difference between revisions of "M-BUS"
From Teknologisk videncenter
m |
m (→Physical layer) |
||
Line 15: | Line 15: | ||
*Plug: No standard | *Plug: No standard | ||
*M-BUS slave example: [https://www.mikroe.com/m-bus-slave-click MIKROE-4137 M-BUS SLAVE CLICK] | *M-BUS slave example: [https://www.mikroe.com/m-bus-slave-click MIKROE-4137 M-BUS SLAVE CLICK] | ||
+ | **Transceiver example: [https://download.mikroe.com/documents/datasheets/tss721a_datasheet.pdf TI-TSS721A] | ||
*M-BUS naster example: [https://www.mikroe.com/m-bus-master-click MIKROE-3880 M-BUS MASTER CLICK] | *M-BUS naster example: [https://www.mikroe.com/m-bus-master-click MIKROE-3880 M-BUS MASTER CLICK] | ||
− | + | ||
*See [https://m-bus.com/documentation-wired/04-physical-layer M-BUS physical layer]] | *See [https://m-bus.com/documentation-wired/04-physical-layer M-BUS physical layer]] |
Revision as of 13:45, 22 December 2022
Meter-BUS or short M-BUS which is designed mainly for remote reading of water meter, gas or electricity meters - not to be confused with Smart-BUS or short S-BUS is designed mainly for home automation |
Physical layer
- Master to slave: 36 Volt = 1 - 24 Volt = 0
- Slave to Master: Draws < 1,5 mA = 1 - draws11-20 mA = 0
- Baudrate: 300 - 9600
- Cable: Two-wire standard telephone cable (JYStY N20.8 mm)
- Max cable length: 350 Meter (Lower baud rates up to 1000 Meter - but restricted power not below 12 V max capacitance 180 nF)
- Power: Up to 27 Watt through the cable = 0,75 A
- Slaves: Up to 250 in a single segment
- Repeater: Also called a master and typically is an M-BUS to RS232 converter attached to a host
- Plug: No standard
- M-BUS slave example: MIKROE-4137 M-BUS SLAVE CLICK
- Transceiver example: TI-TSS721A
- M-BUS naster example: MIKROE-3880 M-BUS MASTER CLICK
- See M-BUS physical layer]
Links
- https://m-bus.com/ (Good documentation)